PRESSURE REDUCING VALVE

Provide a direct acting pressure reducing valve capable of handling inlet pressures up to 357 psi. Valve shall consist of a bronze valve cover threaded to a brass body, pressure adjustment screw, 416 stainless steel floating seat, EPDM seal with Elastomeric diaphragm and internal stainless steel strainer (1000 micron). The wetted surfaces of the valve in contact with consumable water shall contain less than 0.25% of lead by weight and be certified to NSF/ANSI 372. Install pressure reducing valve, with double union end connections, in an easily accessible location for maintenance and in accordance with all applicable codes and standards. Tapped and plugged for downstream pressure gauge. It is recommended to install a “Y” strainer upstream of the pressure reducing valve. Pressure reducing valve shall comply with ASSE Standard 1003. Pressure reducing valve shall be GF Piping Systems’ Model 1319 LF or 1339 LF.